Part 4BondingTouch VoltageBathrooms

Supplementary Bonding and Touch Voltage: When, Where, and Why

IET Wiring Regulations Team ·

Supplementary bonding is one of those topics that generates endless debate on site and in the exam hall. When is it required? Is it still needed in bathrooms? What size conductor? And what exactly is “touch voltage” anyway?

 

This guide cuts through the confusion. We’ll cover what touch voltage means, how supplementary bonding controls it, where BS 7671 requires it, and the practical details of conductor sizing and testing.

 

What Is Touch Voltage?

Touch voltage is the voltage that appears between two simultaneously accessible conductive parts when an earth fault occurs. In simple terms, it’s the voltage a person would experience if they touched two pieces of metalwork at the same time during a fault.

 

Touch voltage — with and without supplementary bonding

 

Why It Matters

Under normal conditions, all metalwork connected to the earthing system should be at the same potential — roughly 0V between any two parts. But during an earth fault, fault current flowing through the protective conductors causes a voltage drop across those conductors. Different pieces of metalwork can end up at different voltages.

 

If a person touches two parts that are at different voltages, current flows through their body. The greater the voltage difference, the greater the shock risk. Regulation 131.2.2 states that persons and livestock shall be protected against dangers that may arise from contact with exposed-conductive-parts or extraneous-conductive-parts.

 

The 50V Limit

BS 7671 uses 50V AC as the conventional touch voltage limit in normal dry conditions (Regulation 411.3.2.2). Below this level, the shock is generally considered non-lethal for healthy adults. In special locations like bathrooms, the limit is effectively lower because of the reduced body resistance when wet.

 

Main Bonding vs Supplementary Bonding

These are two distinct levels of equipotential bonding, and they serve different purposes.

 

Main bonding vs supplementary bonding comparison

 

Main Protective Bonding

Main protective bonding (Regulation 411.3.1.2) connects all incoming metallic services — water, gas, oil, structural steel — to the Main Earthing Terminal (MET) at the origin of the installation. This creates a main equipotential zone throughout the building.

 

  • Required in every installation
  • Connects at the point of entry to the building
  • Minimum conductor size: 6 mm² Cu (10 mm² for PME/TN-C-S supplies per Table 54.8)
  • Handles the bulk of fault current distribution

 

Supplementary Bonding

Supplementary bonding (Regulation 415.2) is a local measure. It connects extraneous-conductive-parts and exposed-conductive-parts within a specific area — typically a bathroom or other special location — to ensure they’re all at the same potential.

 

  • Only required in specific situations (not everywhere)
  • Installed locally within the area of concern
  • Minimum conductor sizes are smaller than main bonding (2.5 or 4 mm²)
  • Limits touch voltage to a safe level even if the main bonding or ADS is insufficient

 

When Is Supplementary Bonding Required?

This is where the regulations have evolved over the years, and it’s a common source of exam questions.

 

The General Rule (Regulation 415.2)

Supplementary bonding is required where automatic disconnection of supply (ADS) cannot be achieved within the required disconnection time, OR where additional protection is deemed necessary for a specific location.

 

Bathrooms (Section 701)

Regulation 701.415.2 is the key regulation for bathrooms. Supplementary bonding is required in locations containing a bath or shower unless:

 

  • All circuits in the location are protected by a 30 mA RCD, AND
  • All extraneous-conductive-parts are connected to the protective equipotential bonding (main bonding) system

 

If both conditions are met, supplementary bonding may be omitted in bathrooms. This was a significant change introduced in the 18th Edition.

 

However, in practice, many electricians still install supplementary bonding in bathrooms as a belt-and-braces approach — especially in older properties where the main bonding may be questionable.

 

Other Locations Requiring Supplementary Bonding

  • Swimming pools and fountains (Section 702) — supplementary bonding is mandatory regardless of RCD protection
  • Agricultural and horticultural premises (Section 705) — supplementary bonding is required in areas accessible to livestock
  • Medical locations (Section 710) — supplementary bonding is required in Group 1 and Group 2 medical locations
  • Any location where disconnection times cannot be met by ADS alone

 

What Gets Bonded?

Understanding the terminology is critical for the exam:

 

TermDefinitionExamples
Exposed-conductive-partMetalwork that forms part of the electrical installation and can be touchedMetal accessory backbox, light fitting body, metal consumer unit enclosure
Extraneous-conductive-partMetalwork NOT part of the electrical installation but capable of introducing a potentialMetal water pipes, gas pipes, radiators, metal baths, structural steelwork

 

Supplementary bonding connects all simultaneously accessible exposed-conductive-parts and extraneous-conductive-parts to each other. The key phrase is “simultaneously accessible” — if a person can touch two metal parts at the same time, they need to be bonded together.

 

Supplementary bonding in a bathroom

 

Conductor Sizes

Regulation 544.2 specifies the minimum conductor sizes for supplementary bonding conductors.

 

Supplementary bonding conductor sizes

 

The Rules

  • Between two extraneous-conductive-parts: minimum 2.5 mm² Cu (if mechanically protected), or 4.0 mm² Cu (if not mechanically protected)
  • Between an exposed-conductive-part and an extraneous-conductive-part: not less than half the cross-sectional area of the circuit protective conductor (CPC) connected to the exposed-conductive-part, with a minimum of 2.5 mm² Cu (protected) or 4.0 mm² Cu (unprotected)

 

Practical Guidance

In most domestic bathroom installations, a 4.0 mm² green/yellow single-core cable is the standard choice. It covers both the “not mechanically protected” requirement and the half-CPC rule for most circuit sizes.

 

Tip: If the CPC of the circuit to a shower is 2.5 mm² (in 6.0/2.5 mm² T&E), half of that is 1.25 mm² — so a 4.0 mm² supplementary bonding conductor is more than adequate.

 

How Supplementary Bonding Reduces Touch Voltage

The physics is straightforward. During an earth fault:

 

  1. Fault current flows through the CPC back to the source
  2. The CPC has resistance, so a voltage develops along it (V = I × R)
  3. The exposed-conductive-part connected to the CPC rises in voltage
  4. Nearby extraneous-conductive-parts (pipes, radiator) may be at a different voltage
  5. The voltage difference between them is the touch voltage

 

By connecting these parts together with a supplementary bonding conductor:

 

  • Both parts are held at approximately the same potential
  • The touch voltage is reduced to the voltage drop across the bonding conductor itself
  • Because the bonding conductor is short and has low resistance, this voltage is very small — typically well below 50V

 

The Formula

The touch voltage between two supplementary bonded parts is approximately:

 

V_touch = I_f × R_bond

 

Where I_f is the fault current and R_bond is the resistance of the bonding conductor. For a 1-metre length of 4.0 mm² copper, R_bond is approximately 0.005 Ω — even with a fault current of 1000A, the touch voltage would only be 5V.

 

Testing Supplementary Bonding

Supplementary bonding must be tested during initial verification (Regulation 612.2) and checked during periodic inspection.

 

Continuity Test

Using a low-resistance ohmmeter:

 

  1. Connect one test lead to the supplementary bonding conductor at one end
  2. Connect the other test lead to the bonding conductor at the other end
  3. The reading should be very low — typically less than 0.05 Ω for short connections

 

Verification of Supplementary Bonding (Regulation 415.2.2)

BS 7671 provides a formula to verify that supplementary bonding is effective:

 

R ≤ 50V ÷ I_a

 

Where:

  • R is the resistance of the supplementary bonding conductor between the two simultaneously accessible parts
  • I_a is the operating current of the protective device (in amps) for a 5-second disconnection time
  • 50V is the conventional touch voltage limit (reduced to 25V in special locations)

 

If the resistance is less than or equal to this value, the supplementary bonding is adequate.

 

Common Mistakes

MistakeProblemSolution
Bonding to plastic pipesPlastic is not conductive — the bond does nothingOnly bond metal extraneous-conductive-parts
Bonding only one endThe bond must be continuous between the two partsVerify continuity at both ends
Using undersize conductorFails to meet Regulation 544.2Use 4 mm² Cu as standard in bathrooms
Missing the bath wasteMetal bath waste pipe is often overlookedBond the metal waste if it’s an extraneous-conductive-part
Assuming all pipes are extraneousPlastic pipes insulate the metal sections from earthCheck if metal pipes actually introduce a potential from outside
Omitting bonding without meeting the exemption criteriaBathroom lacks RCD protection or main bonding is inadequateOnly omit supplementary bonding if ALL exemption conditions are met

 

Exam Quick Reference

QuestionAnswer
”What is touch voltage?”The voltage between two simultaneously accessible conductive parts during a fault
”What is the conventional touch voltage limit?“50V AC (normal conditions)
“When can supplementary bonding be omitted in bathrooms?”When all circuits have 30 mA RCD protection AND all extraneous-conductive-parts are connected to main bonding
”Minimum supplementary bonding conductor (not mechanically protected)?“4.0 mm² Cu
”Minimum supplementary bonding conductor (mechanically protected)?“2.5 mm² Cu
”Key regulation for bathroom supplementary bonding?”Regulation 701.415.2
”Key regulation for supplementary bonding in general?”Regulation 415.2

 

Key Regulations

  • Reg. 411.3.1.2 — Main protective bonding requirements
  • Reg. 411.3.2.2 — Conventional touch voltage limit (50V AC)
  • Reg. 415.2 — Supplementary equipotential bonding (general)
  • Reg. 415.2.2 — Verification of supplementary bonding effectiveness
  • Reg. 544.2 — Supplementary bonding conductor sizing
  • Reg. 612.2 — Continuity of bonding conductors testing
  • Reg. 701.415.2 — Supplementary bonding in bathrooms

 

Practice and Further Study

Supplementary bonding and touch voltage are covered under Part 4: Protection for Safety and Section 701: Bathrooms of BS 7671. Test your knowledge:

 

Study on the go with our mobile app: App Store | Google Play

Prepare for your exam with our mobile app

580+ practice questions with detailed explanations