Part 4Cable SizingEV ChargingSection 722

EV Charger Cable Calculation: A Complete Worked Example

IET Wiring Regulations Team ·

Electric vehicle charger installations are now one of the most common jobs for domestic electricians — and they’re a growing topic in the IET exam. Section 722 of BS 7671 covers the specific requirements for EV charging installations, and it introduces several rules that differ from standard circuit design.

 

This guide walks through a complete cable sizing calculation for a typical domestic 7.4 kW charger, covering every step from design current to earth fault loop impedance verification.

 

EV Charger Types

Before calculating anything, you need to know what you’re installing. Most domestic installations use a Mode 3, single-phase, 7.4 kW charge point — often called a “wallbox.”

 

EV charger types and power requirements

 

Key Points for Cable Sizing

  • 7.4 kW single-phase = 32A at 230V — this is the standard domestic installation
  • 22 kW three-phase = 32A per phase at 400V — commercial premises
  • The charger draws 32A continuously for several hours — this is critical for cable sizing

 

The Continuous Load Problem

Here’s the single most important thing to understand about EV charging: Regulation 722.311 requires EV charging to be treated as a continuous load. This means:

 

  • No diversity is applied — the cable must be rated for the full 32A, not a reduced figure
  • The circuit is assumed to run at full load for 3 hours or more
  • Standard domestic diversity factors (from BS 7671 Table 4A) do not apply to EV circuits

 

This is why a 32A EV circuit often needs a larger cable than a 32A cooker circuit — the cooker gets diversity applied, the EV charger does not.

 

Protection Requirements

Section 722 has specific protection requirements that differ from standard circuits.

 

EV charger protection requirements

 

RCD Protection (Regulation 722.531.3.101)

Every EV charging point must have its own dedicated circuit protected by:

 

  • A 30 mA RCD — minimum Type A (to detect pulsating DC fault currents)
  • If the charger can produce smooth DC leakage greater than 6 mA, a Type B RCD is required
  • Many modern chargers have built-in DC leakage detection, which allows the use of a Type A RCD — check the manufacturer’s documentation

 

Overcurrent Protection

  • A 32A MCB or RCBO (Type B curve is standard) on a dedicated circuit
  • No other loads or socket outlets on the EV circuit
  • An RCBO is the neatest solution as it provides both overcurrent and RCD protection in one device

 

PME Earthing (Regulation 722.411.4.1)

EV charging installations on PME (TN-C-S) supplies have additional earthing considerations. The 18th Edition Amendment 2 now permits PME earthing for EV charging, but you should check with the DNO for any local requirements — particularly for outdoor charge points.

 

Step-by-Step Cable Calculation

Let’s work through a real example.

 

The Scenario

  • Charger: 7.4 kW single-phase wallbox (32A)
  • Cable run: 20 metres from the consumer unit to the garage
  • Installation method: Clipped direct (Method C), with thermal insulation contact on one side for 2 metres through an insulated wall
  • Ambient temperature: 30°C (standard)
  • Earthing system: TN-C-S, Ze = 0.35 Ω
  • Protective device: 32A Type B RCBO

 

EV charger cable calculation — worked example

 

Step 1: Design Current (Ib)

The design current is the maximum current the circuit will carry in normal service.

 

Ib = P ÷ V = 7400 ÷ 230 = 32.17A

 

We round this to 32A since the charger is rated at 32A. The fundamental rule is: Ib ≤ In ≤ It.

 

Step 2: Protective Device Rating (In)

We need In ≥ Ib. A 32A Type B RCBO gives us In = 32A. This satisfies Ib ≤ In.

 

Step 3: Correction Factors

Now we calculate the overall correction factor to determine the minimum tabulated current rating (It) the cable must have.

 

FactorValueReason
Ca (ambient temperature)1.030°C ambient is the reference temperature for PVC cables
Cg (grouping)1.0Single circuit — no grouping derating needed
Ci (thermal insulation)0.75Cable touches thermal insulation on one side (Table 52.2)
Cf (semi-enclosed fuse)1.0Using an MCB/RCBO, not a BS 3036 fuse

 

Overall correction factor = Ca × Cg × Ci = 1.0 × 1.0 × 0.75 = 0.75

 

Step 4: Minimum Tabulated Current (It)

It ≥ In ÷ CF = 32 ÷ 0.75 = 42.67A

 

Now look up the current-carrying capacity tables in Appendix 4 of BS 7671. For T&E cable clipped direct (Reference Method C, Table 4D5):

 

Cable SizeIt (Clipped Direct)
4.0 mm²37A
6.0 mm²47A
10.0 mm²64A

 

4.0 mm² only gives us 37A — that’s less than 42.67A, so it fails. 6.0 mm² gives 47A, which exceeds 42.67A. Select 6.0 mm² T&E.

 

Step 5: Voltage Drop Check

Regulation 525 limits the voltage drop to 5% of the nominal voltage for power circuits, which is:

 

Max VD = 230 × 0.05 = 11.5V

 

From Table 4D5, the mV/A/m value for 6.0 mm² T&E is 7.3 mV/A/m.

 

VD = (mV/A/m × Ib × L) ÷ 1000 = (7.3 × 32 × 20) ÷ 1000 = 4.67V

 

4.67V is well within the 11.5V limit — PASS.

 

Step 6: Earth Fault Loop Impedance (Zs)

Finally, verify that the earth fault loop impedance allows the protective device to disconnect within the required time.

 

Zs = Ze + (R1 + R2)

 

From the resistance tables (at 20°C):

  • R1 for 6.0 mm² = 3.08 mΩ/m
  • R2 for 2.5 mm² CPC = 7.41 mΩ/m
  • R1 + R2 per metre = 10.49 mΩ/m

 

For 20 metres: (R1 + R2) = 10.49 × 20 ÷ 1000 = 0.21 Ω

 

Zs = 0.35 + 0.21 = 0.56 Ω

 

The maximum Zs for a 32A Type B MCB (Table 41.3, 0.4s disconnection) is 1.37 Ω. Our calculated Zs of 0.56 Ω is well within the limit — PASS.

 

EV charger worked example — all steps

 

When to Use SWA Cable

For outdoor or underground cable runs, T&E is not suitable. You should use:

 

  • SWA (Steel Wire Armoured) cable — for buried or exposed outdoor runs
  • Minimum depth: 500 mm below ground (with cable tiles or warning tape)
  • SWA provides its own mechanical protection and can serve as the CPC (the steel wire armour)
  • Common choice: 6.0 mm² 3-core SWA (or 2-core + armour as earth)

 

For runs that are entirely inside the building (e.g., consumer unit to an internal garage), clipped T&E is acceptable.

 

Common Exam Scenarios

ScenarioCable SizeNotes
7.4 kW, 15 m, clipped direct, no derating6.0 mm² T&E4.0 mm² is too small (37A < 42.67A with Ci)
7.4 kW, 30 m, clipped direct, no insulation6.0 mm² T&ECheck voltage drop: 7.3 × 32 × 30 = 7.0V (OK)
7.4 kW, 40 m, clipped direct10.0 mm² T&EVD with 6.0 mm²: 9.3V — tight. Consider 10.0 mm²
7.4 kW, outdoor underground6.0 mm² SWAMust use SWA for external/underground runs
22 kW three-phase, commercial6.0 mm² 5-core SWA32A per phase, check per-phase VD

 

Quick Reference Summary

ParameterValue
Standard domestic EV charger7.4 kW, 32A, single-phase
Protective device32A Type B RCBO (30 mA, Type A minimum)
Diversity factor1.0 (no diversity — continuous load)
Typical cable (internal)6.0 mm² T&E (6242Y)
Typical cable (external)6.0 mm² SWA
Maximum voltage drop5% of 230V = 11.5V
Key BS 7671 sectionSection 722

 

Key Regulations

  • Section 722 — Electric vehicle charging installations (entire section)
  • Reg. 722.311 — Continuous load, diversity not applicable
  • Reg. 722.411.4.1 — Earthing arrangements for PME supplies
  • Reg. 722.531.3.101 — RCD protection requirements (Type A minimum)
  • Reg. 722.433 — Overcurrent protection
  • Table 4D5 — Current-carrying capacity for T&E cables (Reference Method C)
  • Reg. 525 — Voltage drop limits

 

Practice and Further Study

EV charger cable calculation combines Part 4: Protection for Safety with Part 5: Selection and Erection and Section 722 of BS 7671. Test your knowledge:

 

Study on the go with our mobile app: App Store | Google Play

Prepare for your exam with our mobile app

580+ practice questions with detailed explanations